Photovoltaic & Storage

Photovoltaic self consumption

Why protect a photovoltaic installation in buildings against overvoltages?

Photovoltaic (PV) installations in buildings are located on roofs, façades or other building structures. They may be domestic installations, intended for residential buildings, or industrial, designed to meet the energy needs of commercial buildings or industries.

Due to their atmospheric exposure, these systems are more susceptible to damage associated with the effects of lightning. To prevent such damage and subsequent financial and personal losses, lightning and overvoltage protection measures should be considered during the design phase.

Implementing this protection requires taking into account not only the general regulations for installing photovoltaic systems (IEC 60364-7-712), but also the instructions for selecting and installing SPDs (IEC 61643-32), on both the DC and AC sides.

The following aspects are relevant for the correct design and installation of SPDs in these systems:

  • Characteristic data of supply systems, such as network configuration, nominal voltage and short-circuit current.
  • Lightning protection class (LPL) required.
  • Presence of an external lightning protection system and the number of external downpipe conductors.
  • Clearance(s) to be maintained.
  • Location of the inverter and cable lengths between the devices to be protected.

What may be needed for our installation?

We can differentiate two types of installation which determine the type of protection to be used: buildings with external lightning protection and buildings without such a system (SPCR).

Self consumption
Configuration PV in Building with SPCR PV in Building without SPCR
LAC >10 m <10 m >10 m <10 m
LPV >10 m >10 m >10 m <10 m
SPD1 AC Type 1+2 AC Type 1+2 AC Type 2 AC Type 2
SPD2 AC Type 1+2* Not required AC Type 2 Not required
SPD3 PV Type 1+2* PV Type 2* PV Type 2 PV Type 2
SPD4 PV Type 1+2* Not required PV Type 2 Not required

(*) It is sufficient to install type T2 protectors if the clearance(s) is(are) maintained, according to IEC/EN 62305-3, between all cables and elements of the PV system with all parts of the lightning protection system. Surge protectors should be installed as close as possible to the equipment to be protected. When the distance between the modules and the inverter (LPV) and/or between the inverter and the main distribution board (LAC) exceeds 10 m, it is necessary to install an additional protector.

Self consumption
Type PV AC
Type 1+2 PSC YPV PSC 12.5
Type 2 PSM YPV PSM 40

nimbus® Project Designer

The complete protection solution for each application may require an LPS (Lightning Protection System). Our software is free and allows you to do the risk analysis and solve the geometric project with your bill of materials.

You may also like

The overvoltage and lightning laboratory, a tool of innovation and excellence

Since its establishment over 25 years ago, Cirprotec’s high-voltage laboratory has been a global...

30 years of commitment and excellence

We are excited and full of gratitude as we celebrate Cirprotec’s 30th anniversary. This...

EGARA, the new generation of SPDs

We present EGARA, the new generation of Surge Protection Devices (SPD) from the Cirprotec...

Cirprotec at Genera 2024

Last February, we had the privilege of participating in the outstanding Genera 2024 fair...

Need more info?