EGARA 1H LF

Power Line SPDs - DIN RAIL - IEC TYPE 1+2

Type 1+2 surge protection device (SPD) for transient overvoltages, leackage current free with Iimp 25 kA. The certified EGARA 1H LF range is suitable as a first level of protection in buildings with a higher level of risk.

Features

* Suitable as the first level of protection in the main switchboard. Additionally, they can be used in areas with high atmospheric exposure where external protection against direct lightning strikes are already provided.
* Certified range: IEC cert (DEKRA & ENEC).
* Lightning impulse current (10/350 μs): 25 kA per phase
* Nominal discharge current (8/20 μs): 25 kA per phase
* TT, TNC, TNS earthing systems. Uc 255V ideally for 230/400 V networks.
* Visual and remote end of life indication.
* Short-circuit current rating 25kA.
* No back-up fuse up to 250A.
* Monobloc, DIN-rail format.
* New easy ergonomic extraction.
* LCF Leakage current free T1+2 (no electrial loses).
* Distributed PE & Equipotential EBB.
* Shock withstand and vibration-proof: Remote microswitch and DIN-rail anchorage.
* Advanced traceability and in-line automated quality controls of 100% of the SPDs.

Standards and Certifications

IEC/EN 61643-11

iec.svg;ce.svg;rohs.svg;dekra.svg;enec.svg;ukca.svg;weee.svg

Applications

Building
E-Mobility - EV charging
Industry
Photovoltaic and BESS
Telecom
Water treatment
DS-33738239-EGA-1H-255-1+1-LF-IR-EN.pdf;DS-33738343-EGA-1H-255-3+0-LF-IR-EN.pdf;DS-33738451-EGA-1H-255-3+1-LF-IR-EN.pdf