You are here:
- Home
- Surge and Overvoltage
- Actuation on MCB (included)
- V-CHECK MPT
- V-CHECK 4MPT-63 PLUS
V-CHECK 4MPT-63 PLUS
77706465

Protector against transient & permanent overvoltages (EN 50500) (combined), with IGA of 63 A, type 2, 40 kA and three-phase (four-pole).
Technical Data | Value | Units | |
---|---|---|---|
Commercial data | |||
Code | 77706465 | ||
Part Number | V-CHECK 4MPT-63 PLUS | ||
Status | Available | ||
EAN | 8435297809388 | ||
Tariff code (HS) | 8536.30.90 | ||
Dimensions | |||
Packaging height | 80 | [mm] | |
Packaging width | 105 | [mm] | |
Packaging length | 177 | [mm] | |
Packaging weight | 915 | [gr] | |
Packaging unit | 1 | ||
Product height | 90 | [mm] | |
Product width | 162 | [mm] | |
Product length | 70 | [mm] | |
Product weight | 868 | [gr] | |
Surge protection device (SPD) | |||
Designation according to EN 61643-11 | Type 2 | ||
Designation according to IEC 61643-11 | Class II | ||
Maximum continuous operating voltage AC (L-N) | Uc (L-N) | 400 | [V] |
Maximum continuous operating voltage AC (N-PE) | Uc (N-PE) | 254 | [V] |
Maximum discharge current (8/20) (L-N) | Imax (L-N) | 40 | [kA] |
Nominal discharge current (8/20) (L-N) | In (L-N) | 15 | [kA] |
Voltage protection level (L-N) | Up (L-N) | ≤ 1,8 | [kV] |
Voltage protection level (N-PE) | Up (N-PE) | ≤ 1,8 | [kV] |
Response time (L-N) | tA | 25 | [ns] |
Response time (N-PE) | tA | 100 | [ns] |
Visual end of life indication | Yes | ||
Dynamic thermal disconnection (L-N) | Yes | ||
Power frequency overvotlage protector (POP) | |||
According to | EN 50550 | ||
Actuation method | Integrated MCB | ||
Nominal voltage AC 50 Hz (L-N) | Un (L-N) | 230 | [V] |
Nominal voltage AC 50 Hz (L-L) | Un (L-L) | 400 | [V] |
Test button | Yes | ||
Maximum actuation time | tA [Ua = 255 V] | No disparo / No tripping | [s] |
Maximum non-activating time | tA [Ua = 255 V] | No disparo / No tripping | [s] |
Maximum actuation time | tA [Ua = 275 V] | 15 | [s] |
Maximum non-activating time | tA [Ua = 275 V] | 3 | [s] |
Maximum actuation time | tA [Ua = 300 V] | 5 | [s] |
Maximum non-activating time | tA [Ua = 300 V] | 1 | [s] |
Maximum actuation time | tA [Ua = 350 V] | 0,75 | [s] |
Maximum non-activating time | tA [Ua = 350 V] | 0,25 | [s] |
Maximum actuation time | tA [Ua = 400 V] | 0,20 | [s] |
Maximum non-activating time | tA [Ua = 400 V] | 0,07 | [s] |
Torque | 4 | [Nm] | |
Rigid bare wire | 10 | [mm] | |
Flexible bare wire | 10 | [mm] | |
Shunt release torque | 0,7 | [Nm] | |
Rigid bare wire of shunt release | 6 | [mm] | |
Min. rigid conductor section of shunt release | 1,5 | [mm²] | |
Max. rigid conductor section of shunt release | 3,5 | [mm²] | |
Flexible bare wire of shunt release | 6 | [mm] | |
Min. flexible cable section of shunt release | 1,5 | [mm²] | |
Max. flexible conductor section of shunt release | 2,5 | [mm²] | |
Miniature Circuit Breaker (MCB) | |||
Poles | 3P+N | ||
Tripping curve | C | ||
Nominal current | In (IGA) | 63 | [A] |
Nominal voltage (L-N) | Un (L-N) | 230 | [V] |
Nominal voltage (L-L) | Un (L-L) | 400 | [V] |
Nominal frequency | fn | 50 | [Hz] |
Breaking capacity EN 60898 | Icn | 6000 | [A] |
Breaking capacity EN 60947-2 | Icn | 10 | [kA] |
Torque | 4 | [Nm] | |
Rigid bare wire | 14 | [mm] | |
Min. rigid conductor section | 6 | [mm²] | |
Max. rigid conductor section | 35 | [mm²] | |
Flexible bare wire | 14 | [mm] | |
Min. flexible cable section | 6 | [mm²] | |
Max. flexible conductor section | 25 | [mm²] | |
General data | |||
No. poles | 4 | ||
No. DIN rail modules | 9 | ||
Installation | (L-N) | ||
Product standards | EN 50550; IEC 61643-1; EN 61643-11 | ||
Certifications | CE | ||
Housing color | Grey RAL 7035 | ||
Enclosure | IP 20 | ||
Temperature range | -40 ºC ... +60 ºC |