PSM3-30/750 TNC

77707870

CPT-FO-SOBRETENSIONES-PSM3-40-400-TNC-IR-77707867

Select information and download your PDF file

  • General information

  • Additional information

Data sheet

Protector against transient overvoltages, type 2, 750 V, 30 kA (8/20) and three-pole.

Technical Data   Value Units
Commercial data
Code   77707870  
Part Number   PSM3-30/750 TNC  
Status   Available  
EAN   8435297833222  
Tariff code (HS)   8536.30.90  
Dimensions
Product height   90 [mm]
Product width   54 [mm]
Product length   70 [mm]
Product weight   373 [gr]
General data
Internal configuration   3P  
No. poles   3  
No. DIN rail modules   3  
Installation   (L1-L2-L3-PEN)  
Format   Pluggable  
Network configuration   TNC  
Certifications   CE  
Designation according to EN 61643-11   Type 2  
Designation according to IEC 61643-11   Class II  
Insulating material & flammability class   PA66 CT1; V-0  
Enclosure   IP 20  
Temperature range   -40 ºC ... +85 ºC  
Technical features
Supply voltage   690 / - [V]  
Nominal voltage AC 50-60 Hz (L-N) Un (L-N) 690 [V]
Maximum continuous operating voltage (L-PEN) Uc (L-PEN) 750 [V]
Maximum discharge current (8/20) (L-PEN) Imax (L-PEN) 30 [kA]
Nominal discharge current (8/20) (L-PEN) In (L-PEN) 15 [kA]
Nominal discharge current (8/20) In 15 [kA]
Voltage protection level (L-PEN) at In Up (L-PEN) ≤ 3,0 [kV]
Maximum back-up fuse   63 A [gL]
Short circuit withstand Isccr 25 [kA]
Response time (L-PEN) tA (L-PEN) 25 [ns]
Remote indication   No  
Visual end of life indication   Yes  
Dynamic thermal disconnection (L-PEN)   Yes  
UL Technical features
File UL   E360120  
SPD UL Type   2CA  
Power distribution system   3D  
Maximum continuous operating voltage (L-L) MCOV (L-L) 1500 [V]
Maximum continuous operating voltage (L-G) MCOV (L-G) 750 [V]
Nominal discharge current (UL) In 10 [kA]
Voltage protection rating VPR 50 [V]
Voltage protection level (L-L) at In VPR (L-L) 5000 [V]
Voltage protection level (L-G) at In VPR (L-G) 2500 [V]