Insulation monitoring device for photovoltaic systems up to 1000 VDC.

Technical Data   Value Units
Commercial data
Code   77706703  
Part Number   ISO-CHECK PV 1000  
Status   Available  
EAN   8435297832539  
Tariff code (HS)   8536.30.90  
Packaging length   105 [mm]
Dimensions
Packaging height   90 [mm]
Packaging width   127 [mm]
Packaging weight   340 [gr]
Packaging unit   1  
Product height   90 [mm]
Product width   105 [mm]
Product length   70 [mm]
Product weight   295 [gr]
General data
No. DIN rail modules   6  
Format   DIN  
RoHs   Si  
Insulating material & flammability class   PC; V-0  
Enclosure   IP 20  
Temperature range   -25 ºC ... +70 ºC  
Technical features
Type of power supply network   Unearthed DC systems  
Network configuration   IT  
For protection of networks   PV  
Product standards   EN 61557-8; IEC 61557-8  
Aux supply voltage AC 50/60 Hz Us 230 [V]
Power consumption   2 [VA]
Nominal system voltage Un 500 ... 1000 [VDC]
Nominal frequency fn 50 / 60 [Hz]
Maximum back-up fuse   6 A [gG]
Response value Ran 30, 40, 50, 60, 70, 80 [kΩ]
Maximum response time (RLY1) tRLY1 < 1 (Ce ≤22,5 uF) [s]
Response time (RLY2) tRLY2 1, 2, 5, 10 [s]
Relative uncertainty (at 750V<Us<1000V)   5 [%]
Relative uncertainty (at 500V<Us<750V)   15 [%]
Hysteresis (at Un=1.000 VDC; Ran=30 kOhms))   15 [%]
Hysteresis (at Un=1.000 VDC; Ran=80 kOhms))   10 [%]
Reconnection time tr 1 [min]
Measuring voltage (peak value) (RF=Ohm) Um < 25 [V]
Measuring current (RF=0 Ohm) Im < 1,5 [mA]
Internal DC resistance Ri 512 [kΩ]
Internal impedance (at 50 Hz) Zi 512 [kΩ]
Permissible DC voltage Ufg 1150 [V]
System leakage capacitance Ce ≤ 22,5 [uF]
Rated impulse voltage/category Uimp 4 / III [kV]
Compatibilidad electromagnética (CEM)   EN 61000; IEC 61000